SABRE Sickle bladed fans are the latest addition to the Vent-Axia range offering improved pressure characteristics over axial units and lower sound levels. The advanced blade design and purpose built motor ensure excellent reliability and speed control.

Construction

SABRE Plate mounted sickle fans are based on an integrated impeller and external rotor motor design, which produces a very compact unit. Together with a specially designed bell mouth inlet and mounting plate, the complete fan is lightweight and ensures an excellent performance to sound level ratio.

The mounting plate is formed from a single sheet, protected with a tough epoxy paint finish. Inlet finger guards and motor supports are manufactured from steel rod, electro welded for extra strength. Sizes 250 to 710 finger guards give protection to BS 848 Part 5. Manufacture is controlled to BS EN ISO 9001 Standards.

Impellers

The motors and impellers are factory matched, statically and dynamically balanced to ISO 1940, part 1Quality Class G.6.3

Motors

The external rotor motors are specifically designed and styled for this range of fan. Ball bearings are greased for life. Sizes 315 – 710 motors are protected to IP54, against dust and moisture complying with BS EN 60529. They have ribbed aluminium body castings for efficient cooling with Motor insulation to Class ‘F’ (from -40°C to + 70°C). Speed controlled sizes 450 to 710, 6 & 8 pole motors are only suitable for operating temperatures of up to 40°C.

Electrical

The Sabre range is available for either single phase 220-240V 50 Hz capacitor start and run or three phase 380-415V 50Hz. Motors are fitted with Thermal Overload Protection which should be wired into all controller circuits and into starter contactors to prevent motor damage due to overloading / overheating. Units are suitable for speed control by either electronic, voltage reduction or frequency inverters where permissible.

Forms of Running

Vent-Axia Sabre Plate Mounted Sickle fans (VSP) - Forms of Running

Plate mounted fans (ex-stock) are supplied for extract use (Form ‘A’ running).

Terminal Box

An IP54 terminal box is supplied with all models with M20 x 1.5mm gland entry offering protection against dust and water.

Performance

The fan performance, is in accordance with tests to ISO 5801.

Sound Levels

Fan sound levels, measured in a reverberant chamber in accordance with ISO 3744 Part 1. Published dB(A) figures are free field sound pressure levels at 3m with spherical propagation at a reference level of 2 x 10-5Pa (20 micro-Pascal). The sound power level spectra figures are dB with a reference level of 10-12 Watts (1 pico- ~ watt). To ensure minimum noise levels during speed control, an auto transformer speed control is recommended

Typical Specifications

Accessories
A full range of accessories is available with the Sabre Plate mounted Sickle fans:
Electronic Speed Controllers
Auto Transformer Speed Controllers
Inverter Speed Controller
D.O.L. Starters
Louvre Shutters External Guards

 

Dimensions

Dia a b Øc Ød e f g h Øj Kg
250 370 320 256.5 264.5 84 80 6 80 9 3.4
315 430 380 320 328 84 84 19 70 9 6.3
355 485 435 367 372 86 97 21 75 9 7.3
400 540 490 412 420 93 100 12 88 9 10.2
450 575 535 463 480 86 139 14 96 11 15.8
500 655 615 517 528 84 141 16 104 11 17.3
560 725 675 568 589 81 142.5 16 119 11 24
630 805 750 643 664 82 142.5 20 130 11 45
710 850 810 720 763 37 176.5 20 150 14.5 31